What should I set Reheat Type to?
This configuration is only available for sites that have Pelican Zone Controllers (Z8 or Z24) and thermostats that have System Type set to Single Duct Damper.
Reheat Type
This configuration is found under: Admin > Thermostat Configuration > “select any thermostat” > System Type set to Zone Damper > Zone Controller = “select the zone controller the thermostat communicates with” > Damper Settings > Reheat Type
None: If the thermostat is part of a multi-zone system but has no reheat to control.
Open/Close: The thermostat is controlling a Power-Open/Spring-Close or a Power-Open/Power-Close reheat actuator.
The thermostat should be wired to the reheat actuator as follows:
- (W): Reheat rotates Open
- (W2): Reheat rotates Close
Floating: The thermostat is controlling a Floating reheat actuator. You will also need to set the following configurations.
- Actuator Travel Time: Tells the thermostat how many seconds it takes for the reheat to rotate from full closed to full open.
- Maximum Reheat Position: Tells the thermostat what position to place the reheat in when a reheat cycle is active
The thermostat should be wired to the zone damper as follows:
- (W): Reheat rotates Open
- (W2): Reheat rotates Close
The thermostat should be wired to the electric reheat as follows:
- (W): Electric Reheat Enabled
The thermostat should be wired to the reheat as follows:
- (W): Reheat rotates Open or Electric Reheat Enabled
- (W2): Reheat rotates Closed