Activation Differential restricts using the economizer when the outdoor temperature is within that many degrees from the room temperature.
This configuration can be found in the Pelican Web-App > Admin > Thermostat Configuration > ‘select any thermostat‘ > Economizer > Activation Differential.
Configuration options and their meanings:
2°F (default): This restricts using the economizer if the outdoor temperature is within 2°F of the room temperature. For example, if the room temperature is 68°F and the outdoor temperature is 67°F, then an economizer cycle will not start and instead mechanical cooling will be enabled.
Allowable Settings: 0°F, 2°F, 4°F, and 6°F